MODELING NOTES FOR ASHRAE STANDARD 140

© Carrier 2023.  All rights reserved.

===============================================================================
A. SOFTWARE INFORMATION
===============================================================================
1. SOFTWARE VENDOR:   Carrier Corporation

2. SOFTWARE NAME:     Carrier Hourly Analysis Program

3. SOFTWARE VERSION:  6.1.0.1054

4. OPERATING SYSTEM REQUIREMENTS:
                      Windows 10,
                      Windows 11
					  
5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION:
                      Typical = 1 GB

6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION:
                      8 GB

7. MINIMUM DISPLAY MONITOR REQUIREMENTS:
                      XGA with 1024x768 resolution and 256 colors

===============================================================================
B. REPORT BLOCK FOR ALTERNATIVE MODELING METHODS
===============================================================================

NOTE 1 - Adiabatic Bounrady Condition  (5.3.1.4)
---------------------------------------------------------
Simulated Effect:  

Test specifications in 5.3.1.4 requires adding large amount of insulation to the wall, floor and roof assembly to 
model near adiabatic boundary condition.

Alternative Methods: 

Instead of adding insulation to the wall, floor and ceiling material assembly, in the HAP building model,
"unmodeled space" was added on the outside of each surface, in HAP this feature automatically imposes 
adiabatic boundary condition on the surface, therefore it will achieve the same objective as the test
specification.

===============================================================================
C. REPORT BLOCK FOR EQUIVALENT MODELING METHODS
===============================================================================

NONE


===============================================================================
D. REPORT BLOCK FOR USE OF NON-SPECIFIED INPUTS
===============================================================================
 NONE


===============================================================================
E. REPORT BLOCK FOR OMITTED TEST CASES AND RESULTS
===============================================================================

NOTE 1 - Compressor Energy Consumption and Condenser Fan Energy Consumption
         (Section 5.3.1)
-------------------------------------------------------------------------------
1.1 List the Case(s) where Results Were Omitted, and which Results Were Omitted
    for the Case(s):
	
	For all the cases modeled, the compressor energy consumption and the condenser 
	fan power consumption output were omitted, but the total comsumption (include 
	supply fan, compressor, condenser fan) and the supply fan energy consumption
	are reported.


1.2 Explanation for Omitting the Test Case(s) Results:

	In HAP, compressor and condenser fan power are combined, there is no separate output
	for each of them. The combined energy consumption of compressor and condenser fan can
	be calculated by subtracting the supply fan energy consumption (reported in column E) 
	from the total energy consumption (reported in column B). 

===============================================================================
F. REPORT BLOCK FOR CHANGES TO SOURCE CODE FOR THE PURPOSE OF RUNNING THE 
   TESTS, WHERE SUCH CHANGES ARE NOT AVAILABLE IN PUBLICLY RELEASED VERSIONS OF 
   THE SOFTWARE
===============================================================================

NOTE 1 - Cooling System Perfrormance (Full load performance: 5.3.1.10.3; Part Load: 5.3.1.10.4)
-------------------------------------------------------------------------------
1.1 List the Change(s) to the Source Code:
	No modification was made to the source code. However, the changes were made to the HAP 
	generated EnergyPlus input data file to accurately model the cooling system performance 
	as specified in the standard.

1.2 List the Test Case(s) Relevant to the Change(s) in the Source Code:
	All test cases in Section 5-3A.

1.3 Explanation of Why the Change is Not Included in the Publicly Released 
    Version of the Software:

	Originally, there is a set of default cooling system full load and part load performance 
	curves built-in to HAP, this set of performance coefficients are different from what is
	specified in 5.3.1.10. To accurately reflect the cooling system performance specified in 
	section 5.3.1.10.3 and 5.3.1.10.4, the performance tables were converted to lookup tables
	(CE100_DX_CoolingCoilData.IDF) and used to replace the HAP default cooling system performance
	data in the HAP generated EnergyPlus IDF files.
	
	Normally a user would not have enough data for the cooling system to develop a set of 
	performance curves or lookup tables. So HAP does not have a user input to specify the 
	part load performance curve for cooling system.

===============================================================================
G. REPORT BLOCK FOR ANOMALOUS RESULTS
===============================================================================
NONE


===============================================================================